Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
56623 | MICROSEMI CORP.-POWER MANAGEMENT GRO |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3600.0 AC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CQTL | RESET ACTUATOR VOLTAGE RATING AND TYPE IN VOLTS | 115.0 AC |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 SINGLE LOCATION |
ABHP | OVERALL LENGTH | 4.260 INCHES MAXIMUM |
TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
CQQC | TRIP RELEASE DUTY CYCLE | CONTINUOUS SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 115.0 AC SINGLE LOCATION |
CPRQ | RESET METHOD | ELECTRIC |
ABMK | OVERALL WIDTH | 3.250 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
AAQL | BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 71.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.167 INCHES MINIMUM AND 0.177 INCHES MAXIMUM |
CPRJ | TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
CPRK | AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS | 115.0 AC NOMINAL SINGLE LOCATION |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP W/AUXILIARY LOAD TERMINAL AND REMOTE TRIP FEATURE SINGLE LOCATION |
ABKW | OVERALL HEIGHT | 1.200 INCHES MAXIMUM |
FREQ | FREQUENCY IN HERTZ | 400.0 SINGLE LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC SINGLE LOCATION |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |