Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
30086 SPD ELECTRICAL SYSTEMS INC

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CQJX NOMINAL THREAD SIZE 0.250 INCHES
AKPX POLE QUANTITY 3
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 100000.0 AC ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 40.0 AMPERES AC ALL LOCATIONS AND 40.0 AMPERES DC ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
CPRJ TRIP RELEASE METHOD THERMAL ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 THREADED HOLE
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 28.000 MAXIMUM AT 300 PCT ALL LOCATIONS AND 6.000 MINIMUM AT 400 PCT ALL LOCATIONS AND 10.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 30.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 102.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 14.000 MAXIMUM AT 400 PCT ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 QUICK DISCONNECT, FEMALE
CRCF TRIP RELEASE AMBIENT TEMP RATING 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE
CPRP ULTIMATE TRIP TIME PER POLE IN SECONDS 90.000 MINIMUM ALL LOCATIONS AND 540.000 MAXIMUM ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE

Similar Parts

96996A8 , 96996A8 , 5925-00-800-1481 , 5925008001481 , 008001481