Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
3B150 RAYTHEON TECHNICAL SERVICES COMPANY

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM
BBRJ SPECIAL HANDLING FEATURE MAGNETIC
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 2.000 MINIMUM AT 200 PCT SECOND LOCATION AND 20.000 MAXIMUM AT 200 PCT SECOND LOCATION
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC SECOND LOCATION
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SECOND LOCATION
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
AKPX POLE QUANTITY 4
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
CPRH CIRCUIT PROTECTION TYPE UNDERVOLTAGE FOURTH LOCATION
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC THIRD LOCATION
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT THIRD LOCATION
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC SECOND LOCATION
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP FIRST LOCATION
TTQY TERMINAL TYPE AND QUANTITY 8 THREADED STUD
AFJN FRAGILITY FACTOR MODERATELY RUGGED
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC THIRD LOCATION
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 10.0 AMPERES AC THIRD LOCATION
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SECOND LOCATION
FREQ FREQUENCY IN HERTZ 50.0 SECOND LOCATION OR 400.0 SECOND LOCATION
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 2.000 MINIMUM AT 200 PCT FIRST LOCATION AND 20.000 MAXIMUM AT 200 PCT FIRST LOCATION
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 4 TOGGLE
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT AND MOISTURE RESISTANT
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP THIRD LOCATION
AJEC BOSS HEIGHT 0.140 INCHES MINIMUM AND 0.150 INCHES MAXIMUM
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CPRY EXTERNAL ACTUATOR LINKAGE ARRANGEMENT ONE, TWO, THREE, AND FOUR LINKED
ADTV CASE MATERIAL PLASTIC
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC FIRST LOCATION
AXHR MOUNTING FACILITY TYPE AND QUANTITY 8 THREADED HOLE
CPRQ RESET METHOD MANUAL
FREQ FREQUENCY IN HERTZ 50.0 THIRD LOCATION OR 400.0 THIRD LOCATION
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 10.0 AMPERES AC FIRST LOCATION
THSD THREAD SERIES DESIGNATOR UNC
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC FIRST LOCATION
FREQ FREQUENCY IN HERTZ 50.0 FIRST LOCATION OR 400.0 FIRST LOCATION
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY FIRST LOCATION
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM
ADAQ BODY LENGTH 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM
ADAT BODY WIDTH 2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM
PKWT UNPACKAGED UNIT WEIGHT 12.500 OUNCES
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 FIRST LOCATION
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC SECOND LOCATION
APNQ ARC QUENCHING METHOD MAGNETIC BLOWOUT
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 2.000 MINIMUM AT 200 PCT THIRD LOCATION AND 20.000 MAXIMUM AT 200 PCT THIRD LOCATION
AAQL BODY STYLE MULTIPOLE-MULTIPLE ACTUATOR TYPE
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 1000.0 AC THIRD LOCATION
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 10.0 AMPERES AC SECOND LOCATION
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SECOND LOCATION
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 SECOND LOCATION
CMLP THREAD QUANTITY PER INCH 32
CPRJ TRIP RELEASE METHOD MAGNETIC-HYDRAULIC FIRST LOCATION
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT FIRST LOCATION
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY THIRD LOCATION
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 20.0 DC FOURTH LOCATION
CQJX NOMINAL THREAD SIZE 0.138 INCHES
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 THIRD LOCATION

Similar Parts

996302-5 , 9963025 , 5925-01-159-6595 , 5925011596595 , 011596595