Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
58536 FEDERAL COMMERCIAL ITEM DESCRIPTION

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
ADAT BODY WIDTH 2.120 INCHES NOMINAL
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 138.0 SINGLE LOCATION
AAQL BODY STYLE SINGLE POLE TYPE
AFJN FRAGILITY FACTOR MODERATELY RUGGED
TTQY TERMINAL TYPE AND QUANTITY 2 THREADED STUD
TEST TEST DATA DOCUMENT 81349-MIL-C-13516 SPECIFICATION
ZZZK SPECIFICATION/STANDARD DATA 81349--13516/8BII GOVERNMENT SPECIFICATION
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 3.500 INCHES NOMINAL
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
CPRQ RESET METHOD AUTOMATIC
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.220 INCHES NOMINAL
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 575.0 DC SINGLE LOCATION
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.000 INCHES NOMINAL
ADTV CASE MATERIAL PLASTIC
AKPX POLE QUANTITY 1
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 8.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 50.000 MAXIMUM AT 200 PCT SINGLE LOCATION
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 175.0 AMPERES DC SINGLE LOCATION
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.218 INCHES NOMINAL
CPRJ TRIP RELEASE METHOD THERMAL SINGLE LOCATION
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.485 INCHES MINIMUM AND 1.515 INCHES MAXIMUM
ABHP OVERALL LENGTH 4.000 INCHES NOMINAL
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 28.0 DC SINGLE LOCATION
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED SALT SPRAY PROOF AND VIBRATION RESISTANT AND SHOCK RESISTANT AND FUNGUS RESISTANT

Similar Parts