Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
82647 SENSATA TECHNOLOGIES INC

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 138.0 SINGLE LOCATION
AAQL BODY STYLE SINGLE POLE TYPE
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 200.0 AMPERES DC SINGLE LOCATION
AFJN FRAGILITY FACTOR MODERATELY RUGGED
TTQY TERMINAL TYPE AND QUANTITY 2 THREADED STUD
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED CORROSION RESISTANT AND DUSTPROOF AND SHOCK RESISTANT AND VIBRATION RESISTANT
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 3.500 INCHES NOMINAL
CQJX NOMINAL THREAD SIZE 0.190 INCHES
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
ADAT BODY WIDTH 2.125 INCHES NOMINAL
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.219 INCHES NOMINAL
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 THREADED HOLE
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.000 INCHES NOMINAL
ADTV CASE MATERIAL PLASTIC
AKPX POLE QUANTITY 1
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 8.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 50.000 MAXIMUM AT 200 PCT SINGLE LOCATION
CPRQ RESET METHOD MANUAL
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 30.0 DC SINGLE LOCATION
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.500 INCHES NOMINAL
THSD THREAD SERIES DESIGNATOR UNF
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 PUSH BUTTON
FEAT SPECIAL FEATURES MAY ALSO BE USED IN MOST 110 AC APPLICATIONS
CPRJ TRIP RELEASE METHOD THERMAL SINGLE LOCATION
CPRW ACTUATOR FUNCTION TRIP-RESET
ABHP OVERALL LENGTH 4.000 INCHES NOMINAL
CPRX ACTUATOR POSITION DESIGNATION AT POLE ONE
CMLP THREAD QUANTITY PER INCH 32
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
CRCF TRIP RELEASE AMBIENT TEMP RATING 77.0 DEG FAHRENHEIT NOMINAL SINGLE LOCATION
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 3000.0 DC SINGLE LOCATION