Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
89946 EATON CORPORATION

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 240.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
AKPX POLE QUANTITY 3
AXHR MOUNTING FACILITY TYPE AND QUANTITY 6 UNTHREADED HOLE
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS MAXIMUM ALL LOCATIONS
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.188 INCHES NOMINAL
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 100.0 AMPERES AC ALL LOCATIONS AND 100.0 AMPERES DC ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP W/SEPARATE RESET
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 5000.0 AC ALL LOCATIONS AND 5000.0 DC ALL LOCATIONS
CPRX ACTUATOR POSITION DESIGNATION AT EACH POLE
TTQY TERMINAL TYPE AND QUANTITY 6 SCREW
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 110.000 NOMINAL AT 200 PCT ALL LOCATIONS AND 7200.000 NOMINAL AT 125 PCT ALL LOCATIONS AND 23.000 NOMINAL AT 300 PCT ALL LOCATIONS

Similar Parts