Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
30086 | SPD ELECTRICAL SYSTEMS INC |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.594 INCHES NOMINAL |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
AKPX | POLE QUANTITY | 2 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS AND 20.0 AMPERES DC ALL LOCATIONS |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.500 INCHES NOMINAL |
ADAQ | BODY LENGTH | 6.000 INCHES NOMINAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
ADAT | BODY WIDTH | 3.000 INCHES NOMINAL |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 14000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.000 INCHES NOMINAL |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
ADTV | CASE MATERIAL | PLASTIC |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 28.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 65.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.164 INCHES NOMINAL |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
ABXD | BUSHING LENGTH | 0.219 INCHES NOMINAL |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.984 INCHES NOMINAL |