Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
30086 SPD ELECTRICAL SYSTEMS INC

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
ADAU BODY HEIGHT 4.062 INCHES NOMINAL
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 3.000 INCHES NOMINAL
AKPX POLE QUANTITY 2
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 25000.0 AC ALL LOCATIONS AND 20000.0 DC ALL LOCATIONS
ADAT BODY WIDTH 9.000 INCHES NOMINAL
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
CPRJ TRIP RELEASE METHOD THERMAL ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AJEC BOSS HEIGHT 0.250 INCHES NOMINAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 400.0 AMPERES AC ALL LOCATIONS AND 400.0 AMPERES DC ALL LOCATIONS
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 3.000 INCHES NOMINAL
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.250 INCHES NOMINAL
TTQY TERMINAL TYPE AND QUANTITY 6 COMPRESSION
CPRW ACTUATOR FUNCTION TRIP-RESET
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 9.750 INCHES NOMINAL
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 9.875 INCHES NOMINAL
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
ADAQ BODY LENGTH 11.000 INCHES NOMINAL
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 115.0 ALL LOCATIONS
CRCF TRIP RELEASE AMBIENT TEMP RATING 40.0 DEG CELSIUS MAXIMUM ALL LOCATIONS

Similar Parts

ET5739 , ET5739 , 5925-00-025-6005 , 5925000256005 , 000256005