Definition:

AN ELECTROMECHANICAL DEVICE WHICH RELEASES THE HOLDING MECHANISM AND PERMITS THE CONTACTS OF A CIRCUIT BREAKER TO OPEN. IT IS A REPLACEMENT PART OF A CIRCUIT BREAKER. DOES NOT INCLUDE RELAYS. SEE ALSO THERMAL RELEASE, CIRCUIT BREAKER.

CAGE Information

Code Company
30086 SPD ELECTRICAL SYSTEMS INC

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 175.0 AMPERES AC ALL LOCATIONS
AKPX POLE QUANTITY 3
ABKW OVERALL HEIGHT 4.500 INCHES NOMINAL
AXHR MOUNTING FACILITY TYPE AND QUANTITY 6 UNTHREADED HOLE
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 50.000 MAXIMUM AT 500 PCT ALL LOCATIONS
ABMK OVERALL WIDTH 6.688 INCHES NOMINAL
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 105.0 ALL LOCATIONS
ABHP OVERALL LENGTH 8.500 INCHES NOMINAL
CBBL FEATURES PROVIDED ADJUSTABLE TRIP RELEASE
AAQL BODY STYLE RECTANGULAR DIMENSIONAL ENVELOPE
AEBV UNTHREADED MOUNTING HOLE DIAMETER 1.375 INCHES NOMINAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
CRCF TRIP RELEASE AMBIENT TEMP RATING 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 SCREW
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPSF ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS +910.0/+1560.0 AC ALL LOCATIONS
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 500.0 AC ALL LOCATIONS