Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
30086 SPD ELECTRICAL SYSTEMS INC

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
AKPX POLE QUANTITY 3
CSSX SWITCH CURRENT RATING AND TYPE IN AMPS 15.0 AC AND 0.5 DC
CPRZ AUXILIARY SWITCH FUNCTION AND QUANTITY 1 ALARM
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 3.000 INCHES NOMINAL
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 100000.0 AC ALL LOCATIONS
ADAT BODY WIDTH 9.000 INCHES NOMINAL
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 17.000 INCHES NOMINAL
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AJEC BOSS HEIGHT 0.250 INCHES NOMINAL
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 20.000 MINIMUM AT 600 PCT ALL LOCATIONS AND 32.000 MAXIMUM AT 600 PCT ALL LOCATIONS
AEGJ SWITCH CONTACT ARRANGEMENT SINGLE POLE, DOUBLE THROW
CBBL FEATURES PROVIDED ADJUSTABLE TRIP RELEASE
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 3.000 INCHES NOMINAL
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 15.125 INCHES NOMINAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
ABKW OVERALL HEIGHT 11.063 INCHES NOMINAL
CSWP SWITCH VOLTAGE RATING AND TYPE IN VOLTS 460.0 AC AND 125.0 DC
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
CQSM SWITCH LOCATION AND POSITION DESIGNATION INTERNAL AT POLE THREE
FEAT SPECIAL FEATURES SHUNT TRIP 450 VAC
CRCF TRIP RELEASE AMBIENT TEMP RATING 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP-RESET
ADAQ BODY LENGTH 17.938 INCHES NOMINAL
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 THREADED STUD
CPSF ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS +1380.0/+2280.0 AC ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.225 INCHES NOMINAL
CRTK SWITCH TERMINAL TYPE WIRE LEAD
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 500.0 AC ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 350.0 AMPERES AC ALL LOCATIONS
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED GENERAL PURPOSE

Similar Parts

ETN690610S36 , ETN690610S36 , 5925-01-270-2736 , 5925012702736 , 012702736