Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
81348 | FEDERAL SPECIFICATIONS PROMULGATED B |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.380 INCHES NOMINAL |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 30.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 90.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ADAQ | BODY LENGTH | 6.312 INCHES NOMINAL |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
AKPX | POLE QUANTITY | 3 |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
AJEC | BOSS HEIGHT | 0.250 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 4.875 INCHES NOMINAL |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 100.0 AMPERES AC ALL LOCATIONS |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.380 INCHES NOMINAL |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 4.875 INCHES NOMINAL |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 7500.0 AC ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
ADAU | BODY HEIGHT | 3.380 INCHES NOMINAL |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.200 INCHES NOMINAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |