Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
TRIPPER , CIRCUIT BREAKER

Definition:

AN ELECTROMECHANICAL DEVICE WHICH RELEASES THE HOLDING MECHANISM AND PERMITS THE CONTACTS OF A CIRCUIT BREAKER TO OPEN. IT IS A REPLACEMENT PART OF A CIRCUIT BREAKER. DOES NOT INCLUDE RELAYS. SEE ALSO THERMAL RELEASE, CIRCUIT BREAKER.

CAGE Information

Code Company
89946 EATON CORPORATION

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
ABKW OVERALL HEIGHT 5.500 INCHES NOMINAL
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
ABHP OVERALL LENGTH 16.000 INCHES NOMINAL
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
AKPX POLE QUANTITY 3
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 400.0 AMPERES AC ALL LOCATIONS AND 400.0 AMPERES DC ALL LOCATIONS
AAQL BODY STYLE RECTANGULAR DIMENSIONAL ENVELOPE
CPRJ TRIP RELEASE METHOD MAGNETIC ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 COMPRESSION
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
ABMK OVERALL WIDTH 8.250 INCHES NOMINAL
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.344 INCHES NOMINAL
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 110.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 550.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS

Similar Parts

HMA3400T , HMA3400T , 5925-00-449-6965 , 5925004496965 , 004496965