Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
81541 | SENSATA TECHNOLOGIES MARYLAND INC |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
FREQ | FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.835 INCHES MINIMUM AND 1.845 INCHES MAXIMUM |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC ALL LOCATIONS |
AKPX | POLE QUANTITY | 3 |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM |
AJEC | BOSS HEIGHT | 0.125 INCHES MINIMUM AND 0.135 INCHES MAXIMUM |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
ADAQ | BODY LENGTH | 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.655 INCHES MINIMUM AND 1.665 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
ADAT | BODY WIDTH | 2.245 INCHES MINIMUM AND 2.255 INCHES MAXIMUM |
THSD | THREAD SERIES DESIGNATOR | UNC |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 TAB W/SCREW |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.555 INCHES MINIMUM AND 1.565 INCHES MAXIMUM |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 22.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CMLP | THREAD QUANTITY PER INCH | 32 |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |