CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
79500 WESTINGHOUSE ELECTRIC CORP

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
ADAQ BODY LENGTH 6.310 INCHES NOMINAL
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.380 INCHES NOMINAL
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
AKPX POLE QUANTITY 3
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 300.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 2000.000 MAXIMUM AT 150 PCT ALL LOCATIONS
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.312 INCHES NOMINAL
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
AJEC BOSS HEIGHT 0.250 INCHES NOMINAL
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 5.250 INCHES NOMINAL
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.380 INCHES NOMINAL
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 480.0 AC ALL LOCATIONS
CPRJ TRIP RELEASE METHOD MAGNETIC ALL LOCATIONS
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 20000.0 AC ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 COMPRESSION
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
CPRW ACTUATOR FUNCTION TRIP-RESET
ADAU BODY HEIGHT 3.380 INCHES NOMINAL
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 4.880 INCHES NOMINAL
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 225.0 AMPERES AC ALL LOCATIONS
ADAT BODY WIDTH 4.125 INCHES NOMINAL

Similar Parts