Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
98897 LOCKHEED MARTIN CORPORATION DBA LOCK

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CQJX NOMINAL THREAD SIZE 0.469 INCHES
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 2000.0 AC ALL LOCATIONS
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
AXHR MOUNTING FACILITY TYPE AND QUANTITY 1 THREADED BUSHING
AKPX POLE QUANTITY 3
ABXD BUSHING LENGTH 0.281 INCHES MAXIMUM
CPRJ TRIP RELEASE METHOD THERMAL ALL LOCATIONS
ADAQ BODY LENGTH 1.094 INCHES MAXIMUM
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
THSD THREAD SERIES DESIGNATOR UNS
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
ADTV CASE MATERIAL PLASTIC
CPRQ RESET METHOD MANUAL
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 145.0 ALL LOCATIONS
ADAT BODY WIDTH 2.350 INCHES MAXIMUM
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 PUSH-PULL
CPRW ACTUATOR FUNCTION TRIP-RESET
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 0.780 INCHES NOMINAL
ADAU BODY HEIGHT 1.600 INCHES MAXIMUM
TTQY TERMINAL TYPE AND QUANTITY 6 SCREW
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 120.0 AC ALL LOCATIONS
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 2.5 AMPERES AC ALL LOCATIONS
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CMLP THREAD QUANTITY PER INCH 32
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 0.735 INCHES MAXIMUM
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 2.500 MINIMUM AT 200 PCT ALL LOCATIONS AND 40.000 MAXIMUM AT 200 PCT ALL LOCATIONS