Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
81349 MILITARY SPECIFICATIONS PROMULGATED

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 400.0 ALL LOCATIONS
CMLP THREAD QUANTITY PER INCH 24
BBRJ SPECIAL HANDLING FEATURE MAGNETIC
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 15.0 AMPERES AC ALL LOCATIONS
ADAT BODY WIDTH 3.344 INCHES NOMINAL
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
ZZZK SPECIFICATION/STANDARD DATA 81349-MIL-C-17361/4 GOVERNMENT SPECIFICATION
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED SHOCK RESISTANT AND VIBRATION RESISTANT
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 5.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 15.000 MAXIMUM AT 200 PCT ALL LOCATIONS
AKPX POLE QUANTITY 3
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 2.625 INCHES NOMINAL
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 100000.0 AC ALL LOCATIONS
AFJN FRAGILITY FACTOR MODERATELY RUGGED
AJEC BOSS HEIGHT 0.187 INCHES NOMINAL
CQJX NOMINAL THREAD SIZE 0.216 INCHES
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
TEST TEST DATA DOCUMENT 81349-MIL-C-17361 SPECIFICATION
AEHA DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH 1.375 INCHES NOMINAL
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 THREADED HOLE
AEBQ CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH 1.375 INCHES NOMINAL
ADTV CASE MATERIAL PLASTIC
CRCF TRIP RELEASE AMBIENT TEMP RATING 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRQ RESET METHOD MANUAL
APNQ ARC QUENCHING METHOD AIR
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 3.312 INCHES NOMINAL
THSD THREAD SERIES DESIGNATOR UNC
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
ADAU BODY HEIGHT 3.875 INCHES NOMINAL
ADAQ BODY LENGTH 4.125 INCHES NOMINAL
CPRW ACTUATOR FUNCTION TRIP-RESET
FEAT SPECIAL FEATURES CIRCUIT BREAKER SUPPLIED WITH TWO THREADED MOUNTING SCREWS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 QUICK DISCONNECT, MALE
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 150.0 ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
AAQL BODY STYLE MULTIPOLE-SINGLE ACTUATOR TYPE
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 500.0 AC ALL LOCATIONS