CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
81349 MILITARY SPECIFICATIONS PROMULGATED

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED EXPLOSION RESISTANT AND CORROSION RESISTANT
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 138.0 SINGLE LOCATION
AAQL BODY STYLE SINGLE POLE TYPE
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE NONTRIP FREE
TEST TEST DATA DOCUMENT 81349-MIL-C-7079 SPECIFICATION
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
TTQY TERMINAL TYPE AND QUANTITY 2 TAB W/SCREW
CPRP ULTIMATE TRIP TIME PER POLE IN SECONDS 60.000 MAXIMUM SINGLE LOCATION
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 2.000 INCHES MAXIMUM
ADAQ BODY LENGTH 2.189 INCHES MAXIMUM
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 1.812 INCHES NOMINAL
ADTV CASE MATERIAL PLASTIC
AKPX POLE QUANTITY 1
CPRQ RESET METHOD MANUAL
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 30.0 DC SINGLE LOCATION
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 10.0 AMPERES DC SINGLE LOCATION
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 1.188 INCHES NOMINAL
AXHR MOUNTING FACILITY TYPE AND QUANTITY 2 THREADED HOLE
THSD THREAD SERIES DESIGNATOR UNC
CPRJ TRIP RELEASE METHOD THERMAL SINGLE LOCATION
ZZZK SPECIFICATION/STANDARD DATA 96906-MS24506 GOVERNMENT STANDARD
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 PUSH-PULL
CPRW ACTUATOR FUNCTION TRIP-RESET
CPRX ACTUATOR POSITION DESIGNATION AT POLE ONE
ADAT BODY WIDTH 0.750 INCHES MAXIMUM
CMLP THREAD QUANTITY PER INCH 32
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 10.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 50.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION
ABXD BUSHING LENGTH 0.250 INCHES NOMINAL
CQJX NOMINAL THREAD SIZE 0.138 INCHES
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 3000.0 DC SINGLE LOCATION