Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
76374 | EATON CORPORATION DBA FLUID POWER DI |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION AND 1000.0 DC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION AND 1000.0 DC SINGLE LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.469 INCHES |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION AND 32.0 DC SINGLE LOCATION |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES AC SINGLE LOCATION AND 10.0 AMPERES DC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
TTQY | TERMINAL TYPE AND QUANTITY | 2 SCREW |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
AAQL | BODY STYLE | SINGLE POLE TYPE |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
THSD | THREAD SERIES DESIGNATOR | UNS |
ADAQ | BODY LENGTH | 1.380 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.850 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
CPRQ | RESET METHOD | MANUAL |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 5.500 MINIMUM AT 200 PCT SINGLE LOCATION AND 40.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
CPRW | ACTUATOR FUNCTION | RESET |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH BUTTON |
PKWT | UNPACKAGED UNIT WEIGHT | 1.500 OUNCES |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION RESISTANT AND SHOCKPROOF AND VIBRATION RESISTANT |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 145.0 SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
FREQ | FREQUENCY IN HERTZ | 400.0 SINGLE LOCATION |
ADAT | BODY WIDTH | 0.560 INCHES NOMINAL |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.470 INCHES MAXIMUM |
ABXD | BUSHING LENGTH | 0.250 INCHES NOMINAL |