Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
04009 | COOPER INDUSTRIES INC COOPER DISTRIB |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 8.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 75.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
AKPX | POLE QUANTITY | 3 |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 60.0 AMPERES AC ALL LOCATIONS |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
TTQY | TERMINAL TYPE AND QUANTITY | 3 COMPRESSION AND 3 CLIP |
CPRJ | TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 3 CLIP AND 3 TERMINAL |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |