Item Name:
CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
56442 DIAMOND REO TRUCK CO

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
FREQ FREQUENCY IN HERTZ 60.0 SINGLE LOCATION
FREQ FREQUENCY IN HERTZ 60.0 SINGLE LOCATION
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SINGLE LOCATION
AAQL BODY STYLE SINGLE POLE TYPE
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 15.0 AMPERES AC SINGLE LOCATION AND 15.0 AMPERES DC SINGLE LOCATION
AEBY DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH 1.574 INCHES NOMINAL
AJWX MOUNTING SURFACE TO TERMINAL END DISTANCE 1.266 INCHES NOMINAL
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP SINGLE LOCATION
ABHP OVERALL LENGTH 2.000 INCHES NOMINAL
TTQY TERMINAL TYPE AND QUANTITY 2 TAB W/SCREW
ADAT BODY WIDTH 1.250 INCHES NOMINAL
CPRQ RESET METHOD AUTOMATIC
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 130.0 SINGLE LOCATION
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 600.0 AC SINGLE LOCATION AND 600.0 DC SINGLE LOCATION
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 110.0 AC SINGLE LOCATION AND 30.0 DC SINGLE LOCATION
CQXF INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED FUNGUS RESISTANT
ADTV CASE MATERIAL PLASTIC
AKPX POLE QUANTITY 1
AEBP CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH 0.641 INCHES NOMINAL
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.250 INCHES NOMINAL
PKWT UNPACKAGED UNIT WEIGHT 1.500 OUNCES
CPRJ TRIP RELEASE METHOD THERMAL SINGLE LOCATION
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 6.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 45.000 MAXIMUM AT 200 PCT SINGLE LOCATION
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY SINGLE LOCATION
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION
AXHR MOUNTING FACILITY TYPE AND QUANTITY 2 UNTHREADED HOLE