Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
21810 | CHALLENGER ELECTRICAL EQUIPMENT CORP |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 8.093 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
ADAU | BODY HEIGHT | 4.062 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 7.250 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 18.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 45.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS AND 30.0 AMPERES DC ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
AJEC | BOSS HEIGHT | 0.250 INCHES NOMINAL |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 COMPRESSION |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.375 INCHES NOMINAL |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.375 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.250 INCHES NOMINAL |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 9.375 INCHES NOMINAL |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
ADAT | BODY WIDTH | 4.125 INCHES NOMINAL |