Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
89946 | EATON CORPORATION |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
ADAT | BODY WIDTH | 1.000 INCHES MAXIMUM |
ADAT | BODY WIDTH | 1.000 INCHES MAXIMUM |
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
ADAQ | BODY LENGTH | 2.875 INCHES NOMINAL |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION AND TIME DELAY SINGLE LOCATION |
AAQL | BODY STYLE | SINGLE POLE TYPE |
ADAU | BODY HEIGHT | 2.719 INCHES NOMINAL |
TTQY | TERMINAL TYPE AND QUANTITY | 1 COMPRESSION AND 1 TAB, SOLDER LUG |
ABTD | MOUNTING SLOT WIDTH | 0.562 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.187 INCHES NOMINAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
CPRQ | RESET METHOD | MANUAL |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC SINGLE LOCATION |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 100.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC SINGLE LOCATION |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 SLOT |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |