CIRCUIT BREAKER

Definition:

A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.

CAGE Information

Code Company
79500 WESTINGHOUSE ELECTRIC CORP

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CPSM INTERNAL TRIP RELEASE CONFIGURATION SERIES TRIP ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT SECOND LOCATION
ABKW OVERALL HEIGHT 4.688 INCHES NOMINAL
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
AKPX POLE QUANTITY 3
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 250.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
ABHP OVERALL LENGTH 17.688 INCHES NOMINAL
CPRH CIRCUIT PROTECTION TYPE UNDERVOLTAGE THIRD LOCATION
CPRJ TRIP RELEASE METHOD THERMAL ALL LOCATIONS
CPRR MAIN CONTACT TRIPPING MECHANISM TYPE TRIP FREE
CQJX NOMINAL THREAD SIZE 0.375 INCHES
CPRG MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS 10000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 108.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 500.000 MAXIMUM AT 200 PCT ALL LOCATIONS
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 THREADED HOLE
ADTV CASE MATERIAL PLASTIC
AAQL BODY STYLE RECTANGULAR DIMENSIONAL ENVELOPE
CPRQ RESET METHOD MANUAL
CPRL TRIP RELEASE CHARACTERISTIC INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
CMLP THREAD QUANTITY PER INCH 16
THSD THREAD SERIES DESIGNATOR UNC
CPRW ACTUATOR FUNCTION TRIP W/SEPARATE RESET
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
ABMK OVERALL WIDTH 8.250 INCHES NOMINAL
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 125.0 AMPERES AC ALL LOCATIONS AND 125.0 AMPERES DC ALL LOCATIONS
TTQY TERMINAL TYPE AND QUANTITY 6 SCREW
CRCF TRIP RELEASE AMBIENT TEMP RATING 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT FIRST LOCATION