Item Name:
TRIPPER , CIRCUIT BREAKER

Definition:

AN ELECTROMECHANICAL DEVICE WHICH RELEASES THE HOLDING MECHANISM AND PERMITS THE CONTACTS OF A CIRCUIT BREAKER TO OPEN. IT IS A REPLACEMENT PART OF A CIRCUIT BREAKER. DOES NOT INCLUDE RELAYS. SEE ALSO THERMAL RELEASE, CIRCUIT BREAKER.

CAGE Information

Code Company
11660 WESTINGHOUSE ELECTRIC CORP CONTROL B

Federal Supply Class

Title

CIRCUIT BREAKERS

Inclusions:

INCLUDES CIRCUIT BREAKERS AND CUTOUTS.

Exclusions:

EXCLUDES RELAYS.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
ABKW OVERALL HEIGHT 4.062 INCHES NOMINAL
ABHP OVERALL LENGTH 16.000 INCHES NOMINAL
AXHR MOUNTING FACILITY TYPE AND QUANTITY 4 UNTHREADED HOLE
FREQ FREQUENCY IN HERTZ 60.0 ALL LOCATIONS
BBRG STORAGE TYPE GENERAL PURPOSE WAREHOUSE
CPRX ACTUATOR POSITION DESIGNATION AT POLE TWO
AKPX POLE QUANTITY 3
CPRL TRIP RELEASE CHARACTERISTIC TIME DELAY ALL LOCATIONS
CPLM MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE 500.0 AMPERES AC ALL LOCATIONS
AAQL BODY STYLE RECTANGULAR DIMENSIONAL ENVELOPE
TTQY TERMINAL TYPE AND QUANTITY 6 COMPRESSION
CPRJ TRIP RELEASE METHOD THERMAL-MAGNETIC ALL LOCATIONS
CPRN ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT 125.0 ALL LOCATIONS
ABMK OVERALL WIDTH 8.250 INCHES NOMINAL
AEBV UNTHREADED MOUNTING HOLE DIAMETER 0.344 INCHES NOMINAL
CPRW ACTUATOR FUNCTION TRIP-RESET
CQWN TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT 110.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 550.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CPRH CIRCUIT PROTECTION TYPE OVERCURRENT ALL LOCATIONS
CPRT MANUAL ACTUATOR TYPE AND QUANTITY 1 TOGGLE
CPRF OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 600.0 AC ALL LOCATIONS
CRCF TRIP RELEASE AMBIENT TEMP RATING 40.0 DEG CELSIUS MAXIMUM ALL LOCATIONS

Similar Parts

S1605425 , S1605425 , 5925-00-796-6113 , 5925007966113 , 007966113