Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
11660 | WESTINGHOUSE ELECTRIC CORP CONTROL B |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
AJEC | BOSS HEIGHT | 0.500 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
AKPX | POLE QUANTITY | 3 |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 8.437 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 150.0 AMPERES AC ALL LOCATIONS |
ADAT | BODY WIDTH | 5.500 INCHES NOMINAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
ADAQ | BODY LENGTH | 10.138 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
CPRQ | RESET METHOD | MANUAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.281 INCHES NOMINAL |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 170.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 460.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
ADAU | BODY HEIGHT | 3.812 INCHES NOMINAL |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.719 INCHES NOMINAL |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.719 INCHES NOMINAL |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 25000.0 AC ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 8.875 INCHES NOMINAL |