Follow Us on Google+

Request A Price Quote:

Part Number

Part Number:
NSN:
NIIN:
Item Name:
SWITCH , THERMOSTATIC

Definition:

A SWITCH THAT IS ACTUATED BY CHANGES IN AMBIENT TEMPERATURE. EXCLUDES CIRCUIT BREAKER; CONTROL, TEMPERATURE (AS MODIFIED); FUSE (AS MODIFIED); PROTECTOR, THERMAL-OVERLOAD, ELECTRICAL MOTOR; RELAY, THERMAL; AND THERMOSTAT, FLOW CONTROL. SEE ALSO CONTROL, TEMPERATURE (AS MODIFIED) AND REGULATOR, TEMPERATURE (AS MODIFIED).

CAGE Information

Code Company
04845 AUTOMATIC SWITCH COMPANY

Federal Supply Class

Title

SWITCHES

Inclusions:

INCLUDES ROTARY, KNIFE, TOGGLE, PUSH BUTTON, MERCURY, THERMOSTATIC, AND DIFFERENTIAL PRESSURE SWITCHES.

Exclusions:

EXCLUDES SWITCHGEAR.

Characteristics (Decoded)

MRC Requirements Statement Clear Text Reply
ABKW OVERALL HEIGHT 3.500 INCHES NOMINAL
AXGY MOUNTING METHOD FLANGE
AEVT CAPILLARY TUBE LENGTH 72.000 INCHES NOMINAL
AKBY TEMP SENSING ELEMENT TYPE CAPILLARY TUBE-BULB
ABHP OVERALL LENGTH 81.200 INCHES NOMINAL
CTYS CONTACT ADJUSTMENT TYPE EXTERNAL ACTUATION POINT HEX NUT WITH SCALE AND EXTERNAL DEACTUATION POINT HEX NUT WITH SCALE
CBBL FEATURES PROVIDED ELECTRICAL ACCESS PORT
AGAV END ITEM IDENTIFICATION 4930-01-139-2492
CTZB CONTACT VOLTAGE RATING IN VOLTS 125.0 AC AT SEA LEVEL FIRST VOLTAGE
FREQ FREQUENCY IN HERTZ 60.0 FIRST VOLTAGE
CTHF CONTACT LOAD CURRENT RATING 15.0 AMPERES RESISTIVE LOAD FIRST VOLTAGE
CTZB CONTACT VOLTAGE RATING IN VOLTS 250.0 DC AT SEA LEVEL FOURTH VOLTAGE
CTHF CONTACT LOAD CURRENT RATING 10.0 AMPERES RESISTIVE LOAD SECOND VOLTAGE
CSCF TERMINAL TYPE SCREW
CTYM CONTACT ADJUSTMENT RANGE +8.00/+120.00 ACTUATION POINT DEGREES FAHRENHEIT AND +8.00/+120.00 DEACTUATION POINT DEGREES FAHRENHEIT
AEJN DISTANCE BETWEEN MOUNTING FACILITY CENTERS 3.160 INCHES NOMINAL
FEAT SPECIAL FEATURES ALUMINUM SWITCH BODY AND COVER; BUNA-N GASKET
CQGB CONTACT ACTION STIMULUS INCREASE
MEDA MEDIA FOR WHICH DESIGNED GAS OR LIQUID
CRLD NONPILE-UP CONTACT ARRANGEMENT 1 POLE, DOUBLE THROW, BOTH POSITIONS MAINTAINED
STYL STYLE DESIGNATOR CYLINDRICAL W/MOUNTING LUGS
CTYC CONTACT ADJUSTABILITY ACTUATION POINT ADJUSTABLE AND DEACTUATION POINT ADJUSTABLE
ABMK OVERALL WIDTH 4.100 INCHES NOMINAL
CTZB CONTACT VOLTAGE RATING IN VOLTS 125.0 DC AT SEA LEVEL THIRD VOLTAGE
ABFE HAZARDOUS LOCATIONS/ENVIRONMENTAL PROTECTION EXPLOSION PROOF
CTHF CONTACT LOAD CURRENT RATING 0.5 AMPERES RESISTIVE LOAD THIRD VOLTAGE
ADAQ BODY LENGTH 7.600 INCHES NOMINAL
AWTN OPERATING TEMP RATING 100.0 DEG FAHRENHEIT MINIMUM AND 220.0 DEG FAHRENHEIT MAXIMUM
CQYJ MOUNTING FACILITY PATTERN TWO POSITION IN-LINE
FREQ FREQUENCY IN HERTZ 60.0 SECOND VOLTAGE
CTZB CONTACT VOLTAGE RATING IN VOLTS 250.0 AC AT SEA LEVEL SECOND VOLTAGE
AEVV BULB DIAMETER 0.375 INCHES NOMINAL
CTHF CONTACT LOAD CURRENT RATING 0.25 AMPERES RESISTIVE LOAD FOURTH VOLTAGE

Similar Parts

SA12D/QF11A1 , SA12DQF11A1 , 5930-01-450-3048 , 5930014503048 , 014503048