Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
74193 | EATON CORP HEINEMANN PRODUCTS COMMER |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
ADAT | BODY WIDTH | 0.567 INCHES MINIMUM AND 0.629 INCHES MAXIMUM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.870 INCHES MINIMUM AND 0.880 INCHES MAXIMUM |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION PROOF |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
AAQL | BODY STYLE | SINGLE POLE TYPE |
THSD | THREAD SERIES DESIGNATOR | UNEF |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.140 NOMINAL AT 300 PCT SINGLE LOCATION AND 0.080 NOMINAL AT 400 PCT SINGLE LOCATION |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.524 INCHES MINIMUM AND 1.586 INCHES MAXIMUM |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
ADAQ | BODY LENGTH | 1.448 INCHES MINIMUM AND 1.510 INCHES MAXIMUM |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
CPRJ | TRIP RELEASE METHOD | MAGNETIC SINGLE LOCATION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 1.0 AMPERES AC SINGLE LOCATION |
PKWT | UNPACKAGED UNIT WEIGHT | 2.100 OUNCES |
AKPX | POLE QUANTITY | 1 |
CPRQ | RESET METHOD | MANUAL |
TTQY | TERMINAL TYPE AND QUANTITY | 2 WIRE HOOK |
ABXD | BUSHING LENGTH | 0.360 INCHES MINIMUM AND 0.380 INCHES MAXIMUM |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
ADTV | CASE MATERIAL | METAL |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
FREQ | FREQUENCY IN HERTZ | 400.0 SINGLE LOCATION |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING W/PANEL SEAL |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 AC SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |