Part Number
Definition:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.
CAGE Information
Code | Company |
---|---|
77342 | TYCO ELECTRONICS CORPORATION |
Federal Supply Class
Title
CIRCUIT BREAKERS
Inclusions:
INCLUDES CIRCUIT BREAKERS AND CUTOUTS.
Exclusions:
EXCLUDES RELAYS.
Characteristics (Decoded)
MRC | Requirements Statement | Clear Text Reply |
---|---|---|
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC AND 50.0 DC |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.090 INCHES NOMINAL |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | EXTERNAL AT POLE ONE |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.560 INCHES NOMINAL |
AAQL | BODY STYLE | SINGLE POLE TYPE |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
ADAT | BODY WIDTH | 0.750 INCHES NOMINAL |
ADAQ | BODY LENGTH | 2.000 INCHES NOMINAL |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC AND 1.0 DC |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND HUMIDITY RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
CPRQ | RESET METHOD | MANUAL |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 2000.0 DC SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC SINGLE LOCATION |
CRTK | SWITCH TERMINAL TYPE | SOLDER STUD |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 2 QUICK DISCONNECT, MALE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.660 INCHES NOMINAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
AJEC | BOSS HEIGHT | 0.130 INCHES NOMINAL |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 7.0 AMPERES DC SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |